Measured value / Parameter

Parameter name for Speedwire/Webconnect

Parameter name for RS485

Read level

Displayed group in the communication product

Value range / set values

Default value

Step size

Write level

Grid Guard

Parameter

Type of module in module slot

Mdl.Typ

Installer

Device Components > Type Label > Module shaft 1 > Type

  • ------- (None)
  • RS485 module (CmpRS485)
  • Webconnect module (CmpWebConn)

------- (None)

-

Measured value

Condition

Op.Health

User

Status > Operation > Condition

  • Fault (Alm)
  • Off (Off)
  • Ok (Ok)
  • Warning (Wrn)

Off (Off)

-

Measured value

Recommended action

Op.Prio

User

Status > Operation > Current event > Recommended action

  • Contact manufacturer (PrioA)
  • Contact installer (PrioC)
  • invalid (PrioIna)
  • none (NonePrio)

invalid (PrioIna)

-

Measured value

Message

User

Status > Operation > Current event > Message

  • none (NoneMsg)

none (NoneMsg)

-

Measured value

Fault correction measure

User

Status > Operation > Current event > Fault correction measure

  • none (NoneDsc)

none (NoneDsc)

-

Parameter

Find device

User

Device > System > Find device

  • Off (Off)
  • LED blinking (Signal)

Off (Off)

User

-

Parameter

Operating mode of multifunction relay

Mlt.OpMode

User

Device > Multifunction relay > Operating mode

  • Switching status grid relay (GriSwCpy)
  • Fault indication (FltInd)
  • Fan control (FanCtl)
  • Self-consumption (SelfCsmp)
  • Control via communication (ComCtl)
  • Battery bank (BatCha)

Fault indication (FltInd)

User

-

Parameter

Status of MFR with control via communication

Mlt.ComCtl.Sw

User

Device > Multifunction relay > Control via communication > Status

  • Off (Off)
  • On (On)

Off (Off)

User

-

Parameter

Language of the user interface

CntrySet.Lang

User

Device > Country settings > Language

  • Deutsch (LangDE)
  • English (LangEN)
  • Italiano (LangIT)
  • Español (LangES)
  • Français (LangFR)
  • Ελληνικά (LangEL)
  • 한국어 (LangKO)
  • Česky (LangCS)
  • Português (LangPT)
  • Nederlands (LangNL)
  • Slovenski (LangSL)
  • Български (LangBG)
  • Polski (LangPL)
  • 日本語 (LangJA)

English (LangEN)

User

-

Parameter

Update operating mode

Upd.OpMode

Installer

Device > Update > Operating mode

  • Off (Off)
  • On (On)
  • Force (Forc)

On (On)

Installer

-

Measured value

Status of digital inputs of power control module

PCM-DigInStt

User

System and device control > Power control module > Status of digital inputs

  • D1: 0 | D2: 0 | D3: 0 | D4: 0 (DigInD00)
  • D1: 1 | D2: 0 | D3: 0 | D4: 0 (DigInD01)
  • D1: 0 | D2: 1 | D3: 0 | D4: 0 (DigInD02)
  • D1: 1 | D2: 1 | D3: 0 | D4: 0 (DigInD03)
  • D1: 0 | D2: 0 | D3: 1 | D4: 0 (DigInD04)
  • D1: 1 | D2: 0 | D3: 1 | D4: 0 (DigInD05)
  • D1: 0 | D2: 1 | D3: 1 | D4: 0 (DigInD06)
  • D1: 1 | D2: 1 | D3: 1 | D4: 0 (DigInD07)
  • D1: 0 | D2: 0 | D3: 0 | D4: 1 (DigInD08)
  • D1: 1 | D2: 0 | D3: 0 | D4: 1 (DigInD09)
  • D1: 0 | D2: 1 | D3: 0 | D4: 1 (DigInD10)
  • D1: 1 | D2: 1 | D3: 0 | D4: 1 (DigInD11)
  • D1: 0 | D2: 0 | D3: 1 | D4: 1 (DigInD12)
  • D1: 1 | D2: 0 | D3: 1 | D4: 1 (DigInD13)
  • D1: 0 | D2: 1 | D3: 1 | D4: 1 (DigInD14)
  • D1: 1 | D2: 1 | D3: 1 | D4: 1 (DigInD15)

D1: 0 | D2: 0 | D3: 0 | D4: 0 (DigInD00)

-

Parameter

Type of module in the module shaft

Installer

Device Components > Type Label > Module shaft 2 > Type

  • ------- (None)
  • Power control modules (CmpPwrCtlMdul)
  • Emergency power supply modules (CmpEpsMdul)
  • Multifunction relay modules (CmpMfrMdul)

------- (None)

-

Parameter

Firmware version of the communication assembly

KP.swRev

Installer

Device Components > Type Label > Communication assembly > Software version

0 to 4294967294

1

Parameter

Hardware version of the communication assembly

KP.hwRev

Installer

Device Components > Type Label > Communication assembly > Hardware version

0 to 4294967294

1

Parameter

Revision status of the communication assembly

KP.RevVer

Installer

Device Components > Type Label > Communication assembly > Revision status

0 to 255

1

Parameter

Serial number of the communication assembly

Installer

Device Components > Type Label > Communication assembly > Serial number

0 to 4294967294

1

Parameter

SUSyID of the communication assembly

Installer

Device Components > Type Label > Communication assembly > SUSyID

0 to 4294967294

1

Parameter

Firmware version of the Bluetooth component

BT.swRev

Installer

Device Components > Type Label > Bluetooth component > Software version

0 to 4294967294

1

Parameter

Revision status of the Bluetooth component

BT.RevVer

Installer

Device Components > Type Label > Bluetooth component > Revision status

0 to 255

1

Parameter

Serial number of the Bluetooth component

Installer

Device Components > Type Label > Bluetooth component > Serial number

0 to 4294967294

1

Parameter

SUSyID of the Bluetooth component

Installer

Device Components > Type Label > Bluetooth component > SUSyID

0 to 4294967294

1

Parameter

Firmware version of the Zigbee components

ZB.swRev

Installer

Device Components > Type Label > Zigbee components > Software version

0 to 4294967294

1

Parameter

Revision status of the Zigbee components

ZB.RevVer

Installer

Device Components > Type Label > Zigbee components > Revision status

0 to 255

1

Parameter

Serial number of the Zigbee components

Installer

Device Components > Type Label > Zigbee components > Serial number

0 to 4294967294

1

Parameter

SUSyID of the Zigbee components

Installer

Device Components > Type Label > Zigbee components > SUSyID

0 to 4294967294

1

Parameter

Revision status of the display

LCD.RevVer

Installer

Device Components > Type Label > Display > Revision status

0 to 255

1

Parameter

Firmware version of the module

Mdl.swRev

Installer

Device Components > Type Label > Module shaft 1 > Software version

0 to 4294967294

1

Parameter

Hardware version of the module

Mdl.hwRev

Installer

Device Components > Type Label > Module shaft 1 > Hardware version

0 to 4294967294

1

Parameter

Revision status of the module

Mdl.RevVer

Installer

Device Components > Type Label > Module shaft 1 > Revision status

0 to 255

1

Parameter

Serial number of the module

Installer

Device Components > Type Label > Module shaft 1 > Serial number

0 to 4294967294

1

Parameter

SUSyID of the module

Installer

Device Components > Type Label > Module shaft 1 > SUSyID

0 to 4294967294

1

Measured value

Waiting time until feed-in

Op.TmsRmg

User

Status > Operation > Waiting time until feed-in

Measured value

Nominal power in Ok Mode

User

Status > Operation > Device status > Ok

Measured value

Nominal power in Warning Mode

User

Status > Operation > Device status > Warning

Measured value

Nominal power in Fault Mode

User

Status > Operation > Device status > Fault

Measured value

Number of events for user

Op.EvtCntUsr

User

Status > Operation > Events for user

Measured value

Number of events for installer

Op.EvtCntIstl

Installer

Status > Operation > Events for installer

Measured value

Current event number

Op.EvtNo

User

Status > Operation > Current event > Current event number

Measured value

Current event number for manufacturer

Op.EvtNoDvlp

User

Status > Operation > Current event > Event number manufacturer

Parameter

Software package

Pkg.swRev

User

Type Label > Type Label > Software package

0 to 4294967294

1

Measured value

Daily yield

User

AC Side > Measured values > Daily yield

Parameter

Minimum On time for MFR self-consumption

Mlt.MinOnTmm

User

Device > Multifunction relay > Self-consumption > Minimum On time

1 min to 1440 min

120 min

1

User

Parameter

Minimum On power for MFR self-consumption

Mlt.MinOnPwr

User

Device > Multifunction relay > Self-consumption > Minimum On power

100 W to 5000 W

1,500 W

1

User

Parameter

Minimum power On time, MFR self-consumption

Mlt.MinOnPwrTmm

User

Device > Multifunction relay > Self-consumption > Minimum power On time

0 min to 1440 min

30 min

1

User

Parameter

Minimum On power for MFR battery bank

Mlt.BatCha.Pwr

User

Device > Multifunction relay > Battery bank > Minimum On power

100 W to 5000 W

1,500 W

1

User

Parameter

Minimum time before reconnection of MFR battery bank

Mlt.BatCha.Tmm

User

Device > Multifunction relay > Battery bank > Minimum time before reconnection

1 min to 1440 min

30 min

1

User

Parameter

S0 pulses per kWh for feed counter

GM.S0kWhOut

Installer

AC Side > Measured values > Grid measurements > S0 pulses per infed kWh

1 to 4294967294

1

Installer

Parameter

GM.TotkWhOutSet

User

AC Side > Measured values > Grid measurements > Set total yield

0 kWh to 4294967294 kWh

0 kWh

1

User

Measured value

Grid feed-in counter reading

GM.TotWhOut

User

AC Side > Measured values > Grid measurements > Total yield

Measured value

S0-pulses grid feed-in counter

GM.TotS0Out

Installer

AC Side > Measured values > Grid measurements > S0-pulse feed-in

Parameter

Power control module D1: 0 | D2:0 | D3: 0 | D4: 0

Installer

Device > Power control module > Active power limitation > D1: 0 | D2: 0 | D3: 0 | D4: 0

−1 % to +100 %

100 %

1

Installer

Parameter

Power control module D1: 1 | D2:0 | D3: 0 | D4: 0

Installer

Device > Power control module > Active power limitation > D1: 1 | D2: 0 | D3: 0 | D4: 0

−1 % to +100 %

0 %

1

Installer

Parameter

Power control module D1: 0 | D2:1 | D3: 0 | D4: 0

Installer

Device > Power control module > Active power limitation > D1: 0 | D2: 1 | D3: 0 | D4: 0

−1 % to +100 %

30 %

1

Installer

Parameter

Power control module D1: 1 | D2:1 | D3: 0 | D4: 0

Installer

Device > Power control module > Active power limitation > D1: 1 | D2: 1 | D3: 0 | D4: 0

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 0 | D2:0 | D3: 1 | D4: 0

Installer

Device > Power control module > Active power limitation > D1: 0 | D2: 0 | D3: 1 | D4: 0

−1 % to +100 %

60 %

1

Installer

Parameter

Power control module D1: 1 | D2:0 | D3: 1 | D4: 0

Installer

Device > Power control module > Active power limitation > D1: 1 | D2: 0 | D3: 1 | D4: 0

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 0 | D2:1 | D3: 1 | D4: 0

Installer

Device > Power control module > Active power limitation > D1: 0 | D2: 1 | D3: 1 | D4: 0

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 1 | D2:1 | D3: 1 | D4: 0

Installer

Device > Power control module > Active power limitation > D1: 1 | D2: 1 | D3: 1 | D4: 0

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 0 | D2:0 | D3: 0 | D4: 1

Installer

Device > Power control module > Active power limitation > D1: 0 | D2: 0 | D3: 0 | D4: 1

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 1 | D2:0 | D3: 0 | D4: 1

Installer

Device > Power control module > Active power limitation > D1: 1 | D2: 0 | D3: 0 | D4: 1

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 0 | D2:1 | D3: 0 | D4: 1

Installer

Device > Power control module > Active power limitation > D1: 0 | D2: 1 | D3: 0 | D4: 1

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 1 | D2:1 | D3: 0 | D4: 1

Installer

Device > Power control module > Active power limitation > D1: 1 | D2: 1 | D3: 0 | D4: 1

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 0 | D2:0 | D3: 1 | D4: 1

Installer

Device > Power control module > Active power limitation > D1: 0 | D2: 0 | D3: 1 | D4: 1

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 1 | D2:0 | D3: 1 | D4: 1

Installer

Device > Power control module > Active power limitation > D1: 1 | D2: 0 | D3: 1 | D4: 1

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 0 | D2:1 | D3: 1 | D4: 1

Installer

Device > Power control module > Active power limitation > D1: 0 | D2: 1 | D3: 1 | D4: 1

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module D1: 1 | D2:1 | D3: 1 | D4: 1

Installer

Device > Power control module > Active power limitation > D1: 1 | D2: 1 | D3: 1 | D4: 1

−1 % to +100 %

−1 %

1

Installer

Parameter

Power control module release time

Installer

Device > Power control module > Release time

0 h to 99 h

0 h

1

Installer

Parameter

Power control module release value

Installer

Device > Power control module > Release value

−1 % to +100 %

100 %

1

Installer

Parameter

Power control module fault tolerance time

Installer

Device > Power control module > Error tolerance time

1 s to 60 s

5 s

1

Installer

Parameter

Firmware version of the module

Installer

Device Components > Type Label > Module shaft 2 > Software version

0 to 4294967294

1

Parameter

Hardware version of the module

Installer

Device Components > Type Label > Module shaft 2 > Hardware version

0 to 4294967294

1

Parameter

Revision status of the module

Installer

Device Components > Type Label > Module shaft 2 > Revision status

0 to 255

1

Parameter

Serial number of the module

Installer

Device Components > Type Label > Module shaft 2 > Serial number

0 to 4294967294

1

Parameter

SUSyID of module

Installer

Device Components > Type Label > Module shaft 2 > SUSyID

0 to 4294967294

1

Parameter

Fan test

CoolSys.FanTst

Installer

Device > Cooling system > Fan test

  • Off (Off)
  • On (On)

Off (Off)

Installer

-

Measured value

Country standard set

Cntry

User

Grid Monitoring > Grid monitoring > Country standard

  • Special setting (Adj)
  • ‒ (JP50)
  • ‒ (JP60)
  • Information not available (NaNStt)

‒ (JP50)

-

Parameter

Set country standard

CntrySet

Installer

Grid Monitoring > Grid monitoring > Set country standard

  • ‒ (JP50)
  • ‒ (JP60)

Installer

-

Parameter

Activation of active power gradient for reconnection after grid fault

WGraReconEna

Installer

System and device control > Inverter > Curr. active power grad., reconnection, grid fault

  • Off (Off)
  • On (On)

Off (Off)

Installer

-

Parameter

Status of islanding detection frequency monitor

Aid.HzMonStt

Installer

Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Frequency monitoring > Status

  • Off (Off)
  • On (On)

On (On)

Installer

-

Parameter

Status of islanding detection unbalance detection

Aid.AsymDetStt

Installer

Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Unbalance detection > Status

  • Off (Off)
  • On (On)

Off (Off)

Installer

-

Parameter

Login required for GridGuard parameter

Login.Mdt

Installer

Grid Monitoring > Grid monitoring > Country standard > Login prescribed

  • Yes (Yes)
  • No (No)

Yes (Yes)

-

Parameter

Operating mode of dynamic grid support, dynamic grid support configuration

DGS-DGSMod

Installer

System and device control > Inverter > Configuration of dynamic grid support > Operating mode of dynamic grid support

  • Limited dynamic grid support (DGSPa)
  • Full dynamic grid support (DGSFl)

Limited dynamic grid support (DGSPa)

Installer

-

Parameter

Operating mode of stat.V stab., stat.V stab. config.

Q-VArMod

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Operating mode of static voltage stabilization

  • Off (Off)
  • React. power/volt. char. Q(U) (VArCtlVol)
  • Reactive power Q, direct spec. (VArCnstNom)
  • Q specified by PV system control (VArCtlCom)
  • cosPhi, direct specific. (PFCnst)
  • cosPhi, specified by PV system control (PFCtlCom)
  • cosPhi(P) characteristic (PFCtlW)
  • Reactive power/volt. char. Q(U) with meas. points (VArCtlVolCrv)
  • Reactive power charact. curve (CrvMod)
  • cos Phi or Q specification through optimum PV system control (VArPFCtlCom)

Reactive power charact. curve (CrvMod)

Installer

-

Parameter

Excit. type at start point, cosPhi(P) char. conf.

PF-PFExtStr

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Excitation type at starting point

  • Overexcited (OvExt)
  • Underexcited (UnExt)

Overexcited (OvExt)

Installer

-

Parameter

Excit. type at end point, cosPhi(P) char. config.

PF-PFExtStop

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Excitation type at end point

  • Overexcited (OvExt)
  • Underexcited (UnExt)

Underexcited (UnExt)

Installer

-

Parameter

cosPhi excit.type, cosPhi config., direct spec.

PF-PFExt

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi, direct specification > Excitation type of cosPhi

  • Overexcited (OvExt)
  • Underexcited (UnExt)

Underexcited (UnExt)

Installer

-

Parameter

Operating mode of active power reduction in case of overfrequency P(f)

P-WCtlHzMod

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Operating mode active power red., overfreq. P(f)

  • Off (Off)
  • Linear gradient (WCtlHz)
  • Linear gradient of the maximum active power (WCtlHzWMax)

Off (Off)

Installer

-

Parameter

Activation of stay-set indicator function, linear instantaneous power gradient configuration

P-HystEna

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Activation of stay-set indicator function

  • Off (Off)
  • On (On)

Off (Off)

Installer

-

Parameter

Operating mode of feed-in management

P-WMod

Installer

System and device control > Inverter > Configuration of feed-in management > Operating mode Active power

  • Off (Off)
  • Active power limitation P in W (WCnst)
  • Act. power lim. as % of Pmax (WCnstNom)
  • Act. power lim. via PV system ctrl (WCtlCom)

Off (Off)

Installer

-

Parameter

X-axes reference, conf. of grid integration char. 1

UtilCrv1-XRef

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X-axes reference

  • Voltage in V (XRefV)
  • Voltage in percentages of Un (XRefVNom)
  • Seconds (XRefTms)

Voltage in V (XRefV)

Installer

-

Parameter

Y-axes reference, conf. of grid integration char. 1

UtilCrv1-YRef

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y-axes reference

  • Var in percentages of Pmax (YRefVarNom)
  • Power in percentages of Pmax (YRefWNom)
  • Power in percentages of frozen active power (YRefWNomActl)
  • cos Phi (EEI convention) (YRefEEI)

Power in percentages of Pmax (YRefWNom)

Installer

-

Parameter

2nd threshold reference, configuration of characteristic curve mode

UtilCrv2-TrgRef

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Configuration of characteristic curve mode, 2nd characteristic curve > Threshold reference

  • Off (Off)
  • Voltage in V (XRefV)
  • Voltage in percentages of Un (XRefVNom)
  • Active power in watts (XRefW)
  • Active power as a percentage of Pmax (XRefWNom)

Active power as a percentage of Pmax (XRefWNom)

Installer

-

Parameter

Input unit, conf. of grid integration char. 2

UtilCrv2-XRef

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X-axes reference

  • Voltage in V (XRefV)
  • Voltage in percentages of Un (XRefVNom)
  • Seconds (XRefTms)

Voltage in V (XRefV)

Installer

-

Parameter

Output frequency, conf. of grid integration char. 2

UtilCrv2-YRef

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y-axes reference

  • Var in percentages of Pmax (YRefVarNom)
  • Power in percentages of Pmax (YRefWNom)
  • Power in percentages of frozen active power (YRefWNomActl)
  • cos Phi (EEI convention) (YRefEEI)

cos Phi (EEI convention) (YRefEEI)

Installer

-

Parameter

Operating mode of power control module

PCM-OpMode

User

System and device control > Power control module > Operating mode

  • Off (Off)
  • Active power limitation (ModWMax)
  • Remote shut-down (ModRemOff)

Off (Off)

Installer

-

Parameter

Device class

MainModel

User

Type Label > Type Label > Device class

  • Solar Inverters (DevClss1)

Solar Inverters (DevClss1)

-

Parameter

Device type

Model

User

Type Label > Type Label > Device type

  • STP 25000TL-JP-30 (STP 25kTL-JP-30)

STP 25000TL-JP-30 (STP 25kTL-JP-30)

-

Measured value

Grid relay/contactor

Op.GriSwStt

User

Status > Operation > Grid relay status

  • Closed (Cls)
  • Open (Opn)
  • Information not available (NaNStt)

Open (Opn)

-

Parameter

Operating condition

Op.OpModSet

User

Device > Operation > Operating condition

  • MPP (Mpp)
  • Stop (Stop)
  • Constant voltage (VolDCConst)

MPP (Mpp)

Installer

-

Parameter

Load parameter

Op.StoFncSet

Installer

Device > Operation > Load parameter

  • Load preset (DfltParaLod)

Installer

-

Parameter

Reset operating data

Op.FncSetIstl

Installer

Device > Operation > Reset operating data

  • N° grid conn. at grid conn.pt. (GriSwCnt)
  • Reset events (RsEvtCnt)
  • Reset energy logger (RsTotWhLog)
  • Reset operation inhibition (RsPermStoOp)
  • Operating time (TotOpTms)
  • Feed-in time (TotFeedTms)
  • Total yield (TotWhOut)
  • Execute all (DoAll)

Installer

-

Measured value

Derating

Inv.TmpLimStt

User

Status > Operation > Derating

  • Temperature derating (TmpDrt)
  • not active (NoneDrt)
  • Information not available (NaNStt)

not active (NoneDrt)

-

Measured value

Status, device control

InvCtl.Stt

User

Status > Operation > Device control > Status

  • Off (Off)
  • On (On)
  • Active (Act)

Off (Off)

-

Measured value

Status, PV system control

PlntCtl.Stt

User

Status > Operation > PV system control > Status

  • Off (Off)
  • On (On)
  • Active (Act)

Off (Off)

-

Parameter

Manual restart activated

ManRstr.IsOn

Installer

AC Side > Operation > Manual restart > Activated

  • Yes (Yes)
  • No (No)

No (No)

Installer

-

Parameter

Manual restart after overvoltage

ManRstr.OvVol

Installer

AC Side > Operation > Manual restart > After overvoltage

  • Off (Off)
  • On (On)

Off (Off)

Installer

-

Parameter

Manual restart after undervoltage

ManRstr.UnVol

Installer

AC Side > Operation > Manual restart > After undervoltage

  • Off (Off)
  • On (On)

Off (Off)

Installer

-

Parameter

Manual restart after frequency error

ManRstr.Hz

Installer

AC Side > Operation > Manual restart > After frequency error

  • Off (Off)
  • On (On)

Off (Off)

Installer

-

Parameter

Manual restart after passive islanding detection

ManRstr.PID

Installer

AC Side > Operation > Manual restart > After passive islanding detection

  • Off (Off)
  • On (On)

Off (Off)

Installer

-

Parameter

Manual restart after active islanding detection

ManRstr.AID

Installer

AC Side > Operation > Manual restart > After active islanding detection

  • Off (Off)
  • On (On)

Off (Off)

Installer

-

Measured value

Restart block status

ManRstr.LokStt

User

Status > Operation > Restart block status

  • Grid frequency disturbance (EvtAcHz)
  • ------- (None)
  • Overvoltage (OvVol)
  • Undervoltage (UnVol)
  • Passive island detection (PID)
  • Active island detection (ActIsldDet)
  • Information not available (NaNStt)

------- (None)

-

Parameter

Reactive current droop, full dynamic grid support configuration

DGS-ArGraMod

Installer

System and device control > Inverter > Configuration of dynamic grid support > Configuration of full dynamic grid support > Reactive current droop

  • SDLWindV (SDLWindV)
  • Medium-Voltage Directive (Germany) (MVtgDirective)

Medium-Voltage Directive (Germany) (MVtgDirective)

Installer

-

Parameter

Grid disconn. at 0% specif. by feeding management

P-GriSwOpnZerW

Installer

System and device control > Inverter > Configuration of feed-in management > Grid disconnection for 0% feeding

  • Yes (Yes)
  • No (No)
  • Yes, with manual restart (YesManRstr)

No (No)

Installer

-

Parameter

Reactive power droop mode, reactive power/voltage characteristic curve configuration Q(U)

Q-VArGraMod

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Reactive power droop mode

  • Hysteresis (Hyst)
  • Dead band (Db)

Hysteresis (Hyst)

Installer

-

Parameter

OptiTrac Global Peak switched on

MPPShdw.IsOn

User

DC Side > DC settings > OptiTrac Global Peak > Activated

  • Yes (Yes)
  • No (No)

Yes (Yes)

User

-

Parameter

Operating mode for absent active power limitation

WCtlCom.MssMod

Installer

System and device control > Inverter > Configuration of system control via communication > Act. power lim. via PV system ctrl > Operating mode for absent system control

  • Values maintained (UsStp)
  • Use fallback setting (UsFlb)

Values maintained (UsStp)

Installer

-

Parameter

Operating mode for absent reactive power control

QCtlCom.MssMod

Installer

System and device control > Inverter > Configuration of system control via communication > Q specified by PV system control > Operating mode for absent system control

  • Values maintained (UsStp)
  • Use fallback setting (UsFlb)

Values maintained (UsStp)

Installer

-

Parameter

Operating mode for absent cos Phi spec

PFCtlCom.MssMod

Installer

System and device control > Inverter > Configuration of system control via communication > cosPhi, specified by PV system control > Operating mode for absent system control

  • Values maintained (UsStp)
  • Use fallback setting (UsFlb)

Values maintained (UsStp)

Installer

-

Parameter

Fallback stimulation type for absent cos Phi spec

PFCtlCom.FlbExt

Installer

System and device control > Inverter > Configuration of system control via communication > cosPhi, specified by PV system control > Fallback excitation type

  • Overexcited (OvExt)
  • Underexcited (UnExt)

Underexcited (UnExt)

Installer

-

Measured value

Current spec. stimulation type cos Phi

Op.Dmd.PFExtCtl

User

System and device control > Operation > Specification > Excitation type cos Phi

  • Overexcited (OvExt)
  • Underexcited (UnExt)
  • Information not available (NaNStt)

Information not available (NaNStt)

-

Parameter

Oper.mode vol.maint.at Q on Dem., st.vol.maint.conf.

Q-VArModDmd

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Operating mode of the stat.volt.maint. for Q on demand

  • Off (Off)
  • As static voltage stability (VArModRef)

Off (Off)

Installer

-

Parameter

Impedance compensation switched on

ImpCpn.IsOn

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Impedance compensation > Activated

  • Yes (Yes)
  • No (No)

No (No)

Installer

-

Measured value

Operating condition temperatures

User

Device > Cooling system > Operating condition temperatures

Measured value

DC current input

A1.Ms.Amp, A2.Ms.Amp, A3.Ms.Amp, A4.Ms.Amp, A5.Ms.Amp, B1.Ms.Amp, A.Ms.Amp, B.Ms.Amp

User

DC Side > DC measurements > Current

Measured value

Operating condition DC current input

User

DC Side > DC measurements > Operating condition current

Measured value

DC voltage input

A.Ms.Vol, B.Ms.Vol

User

DC Side > DC measurements > Voltage

Measured value

Operating condition DC voltage input

User

DC Side > DC measurements > Operating condition voltage

Measured value

DC power input

A.Ms.Watt, B.Ms.Watt

User

DC Side > DC measurements > Power

Measured value

Operating condition DC power input

User

DC Side > DC measurements > Operating condition power

Parameter

Start delay input

A.StrTms, B.StrTms

Installer

DC Side > DC settings > Start delay

1 s to 4 s

1 s

1

Installer

Parameter

Minimum voltage input

A.VStr, B.VStr

Installer

DC Side > DC settings > Critical voltage to start feed-in

188.00 V to 800.00 V

188.00 V

0.01

Installer

Parameter

Constant voltage setpoint

A.Const.VSet, B.Const.VSet

Installer

DC Side > DC settings > Constant voltage control > Voltage setpoint

150.00 V to 1000.00 V

1,000.00 V

0.01

Installer

Parameter

Grid nominal voltage

VRtg

Installer

Grid Monitoring > Grid monitoring > Country standard > Nominal voltage

100 V to 480 V

Depending on the country data set

1

InstallerSMA Grid Guard

Parameter

Nominal frequency

HzRtg

Installer

Grid Monitoring > Grid monitoring > Country standard > Nominal frequency

44.00 Hz to 65.00 Hz

Depending on the country data set

0.01

InstallerSMA Grid Guard

Parameter

Reconnection time upon restart

GriStrTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Reconnection time upon restart

0.000 s to 1600.000 s

300.000 s

0.001

InstallerSMA Grid Guard

Parameter

Reconnection time upon grid interruption

GriFltMonTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Reconnection time upon grid interruption

0.000 s to 1600.000 s

300.000 s

0.001

InstallerSMA Grid Guard

Parameter

Reconnection time upon short interruption

GriFltReConTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Reconnection time upon short interruption

0.000 s to 1600.000 s

300.000 s

0.001

InstallerSMA Grid Guard

Parameter

Maximum duration of a short interruption

GriFltTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Maximum duration of a short interruption

0.000 s to 400.000 s

3.000 s

0.001

InstallerSMA Grid Guard

Parameter

Tripping threshold DC current monitoring

AMaxOfs

Installer

Grid Monitoring > Grid monitoring > Country standard > Tripping threshold DC current monitoring

0.020 A to 2.000 A

0.362 A

0.001

InstallerSMA Grid Guard

Parameter

Tripping time DC current monitoring

AMaxOfsTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Tripping time DC current monitoring

100 ms to 10000 ms

500 ms

1

InstallerSMA Grid Guard

Parameter

Minimum insulation resistance

Iso.LeakRisMin

Installer

Grid Monitoring > Grid monitoring > Country standard > Minimum insulation resistance

100000 Ω to 1000000 Ω

200,000 Ω

1

InstallerSMA Grid Guard

Parameter

Active power gradient connection

WGraConn

Installer

System and device control > Inverter > Active power gradient connection

1 % to 10000 %

1,200 %

1

InstallerSMA Grid Guard

Parameter

Reconnect gradient after grid fault

WGraRecon

Installer

System and device control > Inverter > Power gradient for reconnection after grid fault

1 % to 10000 %

1,200 %

1

InstallerSMA Grid Guard

Parameter

Tripping time of islanding detection frq. monitor

Aid.HzMonTmms

Installer

Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Frequency monitoring > Tripping time of the frequency monitor

0 ms to 10000 ms

600 ms

1

InstallerSMA Grid Guard

Parameter

Permissible grid unbalance of islanding detection

Aid.AsymDetMax

Installer

Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Unbalance detection > Permissible grid unbalance

0 % to 50 %

50 %

1

InstallerSMA Grid Guard

Parameter

Trip.time of islanding detection unbalance detect.

Aid.AsymDetMaxT

Installer

Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Unbalance detection > Tripping time of the unbalance detection

0 ms to 10000 ms

10,000 ms

1

InstallerSMA Grid Guard

Parameter

Voltage monitoring upper maximum threshold

VolCtl.Max

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper maximum threshold

300.00 V to 480.00 V

480.00 V

0.01

InstallerSMA Grid Guard

Parameter

Voltage monitoring upper max. threshold trip. time

VolCtl.MaxTmms

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper maximum threshold tripping time

0.100 ms to 5.000 ms

0.312 ms

0.001

InstallerSMA Grid Guard

Parameter

Voltage monitoring median maximum threshold

VolCtl.hhLim

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Median maximum threshold

175.00 V to 520.00 V

520.00 V

0.01

InstallerSMA Grid Guard

Parameter

Voltage monitoring median max. threshold trip.time

VolCtl.hhLimTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Median maximum threshold tripping time

0 ms to 60000 ms

100 ms

1

InstallerSMA Grid Guard

Parameter

Voltage monitoring lower maximum threshold

VolCtl.hLim

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Lower maximum threshold

175.00 V to 520.00 V

Depending on the country data set

0.01

InstallerSMA Grid Guard

Parameter

Voltage monitoring lower max. threshold trip. time

VolCtl.hLimTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Lower maximum threshold tripping time

0 ms to 60000 ms

1,000 ms

1

InstallerSMA Grid Guard

Parameter

Voltage monitoring lower minimum threshold

VolCtl.lLim

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper minimum threshold

75.00 V to 440.00 V

Depending on the country data set

0.01

InstallerSMA Grid Guard

Parameter

Voltage monitoring lower min. threshold trip. time

VolCtl.lLimTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper minimum threshold tripping time

0 ms to 10000 ms

1,000 ms

1

InstallerSMA Grid Guard

Parameter

Voltage monitoring of median minimum threshold

VolCtl.llLim

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Median minimum threshold

75.00 V to 455.00 V

75.00 V

0.01

InstallerSMA Grid Guard

Parameter

Voltage monitoring median min. threshold trip.time

VolCtl.llLimTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Median minimum threshold tripping time

0 ms to 60000 ms

10,000 ms

1

InstallerSMA Grid Guard

Parameter

Voltage increase protection

VolCtl.Rpro

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Voltage increase protection

100.00 V to 600.00 V

280.00 V

0.01

InstallerSMA Grid Guard

Parameter

Min. voltage for reconnection

VolCtl.ReconMin

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Lower reconnection limit

45.00 V to 240.00 V

45.00 V

0.01

InstallerSMA Grid Guard

Parameter

Max. voltage for reconnection

VolCtl.ReconMax

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper limit for reconnection

100.00 V to 600.00 V

555.00 V

0.01

InstallerSMA Grid Guard

Parameter

Frequency monitoring median maximum threshold

FrqCtl.hhLim

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Median maximum threshold

50.00 Hz to 65.00 Hz

65.00 Hz

0.01

InstallerSMA Grid Guard

Parameter

Frq. monitoring median max. threshold trip. time

FrqCtl.hhLimTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Median maximum threshold tripping time

0 ms to 10000 ms

10,000 ms

1

InstallerSMA Grid Guard

Parameter

Frequency monitoring lower maximum threshold

FrqCtl.hLim

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Lower maximum threshold

50.00 Hz to 65.00 Hz

Depending on the country data set

0.01

InstallerSMA Grid Guard

Parameter

Frq. monitoring lower max. threshold trip. time

FrqCtl.hLimTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Lower maximum threshold tripping time

0 ms to 2000 ms

1,000 ms

1

InstallerSMA Grid Guard

Parameter

Frequency monitoring upper minimum threshold

FrqCtl.lLim

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Upper minimum threshold

44.00 Hz to 60.00 Hz

Depending on the country data set

0.01

InstallerSMA Grid Guard

Parameter

Frq. monitoring upper min. threshold trip. time

FrqCtl.lLimTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Upper minimum threshold tripping time

0 ms to 2000 ms

1,000 ms

1

InstallerSMA Grid Guard

Parameter

Frequency monitoring median minimum threshold

FrqCtl.llLim

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Median minimum threshold

44.00 Hz to 60.00 Hz

44.00 Hz

0.01

InstallerSMA Grid Guard

Parameter

Frq. monitoring median min. threshold trip. time

FrqCtl.llLimTms

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Median minimum threshold tripping time

0 ms to 300000 ms

300,000 ms

1

InstallerSMA Grid Guard

Parameter

Maximum allowable frequency drift

FrqCtl.ChgMax

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Max. frequency change per second

0.00 Hz to 10.00 Hz

0.20 Hz

0.01

InstallerSMA Grid Guard

Parameter

Tripping time when exceeding max. frequency drift

FrqCtl.ChgMaxTm

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Tripping time for max. frequency change per second

0 ms to 10000 ms

440 ms

1

InstallerSMA Grid Guard

Parameter

Lower frequency for reconnection

FrqCtl.ReconMin

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Lower reconnection limit

44.00 Hz to 60.00 Hz

44.00 Hz

0.01

InstallerSMA Grid Guard

Parameter

Upper frequency for reconnection

FrqCtl.ReconMax

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Upper limit for reconnection

50.00 Hz to 65.00 Hz

65.00 Hz

0.01

InstallerSMA Grid Guard

Parameter

Hysteresis voltage, dynamic grid support configuration

DGS-HystVolNom

Installer

System and device control > Inverter > Configuration of dynamic grid support > Hysteresis voltage

0 % to 100 %

5 %

1

InstallerSMA Grid Guard

Parameter

PWM inverse voltage, dynamic grid support configuration

DGS-PWMVolNom

Installer

System and device control > Inverter > Configuration of dynamic grid support > PWM inverse voltage

0 % to 100 %

15 %

1

InstallerSMA Grid Guard

Parameter

cosPhi at start point, cosPhi(P) char. config.

PF-PFStr

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > cosPhi of start point

0.80 to 1.00

1.00 

0.01

InstallerSMA Grid Guard

Parameter

Act. power at start point, cosPhi(P) char. config.

PF-WNomStr

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Active power at starting point

0 % to 100 %

50 %

1

InstallerSMA Grid Guard

Parameter

cosPhi at end point, cosPhi(P) char. config.

PF-PFStop

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > cosPhi of end point

0.80 to 1.00

1.00 

0.01

InstallerSMA Grid Guard

Parameter

Act. power at end point, cosPhi(P) char. config.

PF-WNomStop

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Active power at end point

0 % to 100 %

100 %

1

InstallerSMA Grid Guard

Parameter

Activating voltage, cosPhi(P) char. conf.

PF-EnaVol

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Activating voltage

0.0 % to 120.0 %

100.0 %

0.1

InstallerSMA Grid Guard

Parameter

Deactivating voltage, cosPhi(P) char. conf.

PF-DsaVol

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Deactivating voltage

0.0 % to 120.0 %

100.0 %

0.1

InstallerSMA Grid Guard

Parameter

cosPhi setpoint, cosPhi config., direct specif.

PF-PF

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi, direct specification > cosPhi specification

0.80 to 1.00

1.00 

0.01

InstallerSMA Grid Guard

Parameter

Waiting time of active power grad. after reset frequency, conf. of linear instantaneous power gradient

P-HzStopWGraTms

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Min. time until activation of active power gradient after reset frequency

0 s to 1600 s

0 s

1

InstallerSMA Grid Guard

Parameter

Lower frequency limit prior to end of active power reduction, linear instant. power gradient conf.

P-HzStopMin

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Lower frequ. deviation limit prior to active power release

−5.00 Hz to 0.00 Hz

−5.00 Hz

0.01

InstallerSMA Grid Guard

Parameter

Upper frequency limit prior to end of active power reduction, linear instant. power gradient conf.

P-HzStopMax

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Upper frequ. dev. limit prior to active power release

0.00 Hz to 5.00 Hz

5.00 Hz

0.01

InstallerSMA Grid Guard

Parameter

Active power gradient after reset frequency, linear instantaneous power gradient configuration

P-HzStopWGra

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Active power gradient after reset frequency

1 % to 10000 %

10,000 %

1

InstallerSMA Grid Guard

Parameter

Difference between starting frequency and grid frequency, linear instantaneous power gradient configuration

P-HzStr

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Difference between starting freq. and grid freq.

0.00 Hz to 5.00 Hz

0.20 Hz

0.01

InstallerSMA Grid Guard

Parameter

Difference between reset frequency and grid frequency, linear instantaneous power gradient configuration

P-HzStop

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Difference between reset frequency and grid freq.

0.00 Hz to 5.00 Hz

0.05 Hz

0.01

InstallerSMA Grid Guard

Parameter

Active power gradient, linear instantaneous power gradient configuration

P-WGra

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Active power gradient

10 % to 130 %

40 %

1

InstallerSMA Grid Guard

Parameter

Characteristic curve number, configuration of characteristic curve mode

UtilCrv-CrvNum

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Configuration of characteristic curve mode > Characteristic curve number

0 to 2

1

InstallerSMA Grid Guard

Parameter

Number of points to be used, conf. of grid integr. char. 1

UtilCrv1-NumPt

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Number of points to be used

1 to 8

1

InstallerSMA Grid Guard

Parameter

X value 1, conf. of grid integr. char. 1

UtilCrv1-XVal1

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 1

70.000 to 550.000

Depending on the country data set

0.001

InstallerSMA Grid Guard

Parameter

Y value 1, conf. of grid integr. char. 1

UtilCrv1-YVal1

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 1

−100.000 to +100.000

100.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 2, conf. of grid integr. char. 1

UtilCrv1-XVal2

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 2

70.000 to 550.000

Depending on the country data set

0.001

InstallerSMA Grid Guard

Parameter

Y value 2, conf. of grid integr. char. 1

UtilCrv1-YVal2

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 2

−100.000 to +100.000

0.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 3, conf. of grid integr. char. 1

UtilCrv1-XVal3

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 3

70.000 to 550.000

490.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 3, conf. of grid integr. char. 1

UtilCrv1-YVal3

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 3

−100.000 to +100.000

100.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 4, conf. of grid integr. char. 1

UtilCrv1-XVal4

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 4

70.000 to 550.000

490.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 4, conf. of grid integr. char. 1

UtilCrv1-YVal4

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 4

−100.000 to +100.000

100.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 5, conf. of grid integr. char. 1

UtilCrv1-XVal5

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 5

70.000 to 550.000

490.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 5, conf. of grid integr. char. 1

UtilCrv1-YVal5

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 5

−100.000 to +100.000

100.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 6, conf. of grid integr. char. 1

UtilCrv1-XVal6

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 6

70.000 to 550.000

490.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 6, conf. of grid integr. char. 1

UtilCrv1-YVal6

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 6

−100.000 to +100.000

100.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 7, conf. of grid integr. char. 1

UtilCrv1-XVal7

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 7

70.000 to 550.000

490.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 7, conf. of grid integr. char. 1

UtilCrv1-YVal7

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 7

−100.000 to +100.000

100.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 8, conf. of grid integr. char. 1

UtilCrv1-XVal8

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 8

70.000 to 550.000

490.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 8, conf. of grid integr. char. 1

UtilCrv1-YVal8

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 8

−100.000 to +100.000

100.000 

0.001

InstallerSMA Grid Guard

Parameter

Adjustment time of characteristic operating point, conf. of grid integr. char. 1

UtilCrv1-CrvTms

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Adjustm. time characteristic curve operating point

0.0 s to 1000.0 s

0.0 s

0.1

InstallerSMA Grid Guard

Parameter

Decrease ramp, conf. of grid integr. char. 1

UtilCrv1-RmpDec

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Decrease ramp

1.0 % to 10000.0 %

20.0 %

0.1

InstallerSMA Grid Guard

Parameter

Increase ramp, conf. of grid integr. char. 1

UtilCrv1-RmpInc

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Increase ramp

1.0 % to 10000.0 %

100.0 %

0.1

InstallerSMA Grid Guard

Parameter

2nd characteristic curve number, configuration of characteristic curve mode

UtilCrv2-CrvNum

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Configuration of characteristic curve mode, 2nd characteristic curve > Characteristic curve number

0 to 2

1

InstallerSMA Grid Guard

Parameter

2nd activation threshold, configuration of characteristic curve mode

UtilCrv2-EnaTrg

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Configuration of characteristic curve mode, 2nd characteristic curve > Activation threshold

0.000 to 100.000

15.000 

0.001

InstallerSMA Grid Guard

Parameter

2nd deactivation threshold, configuration of characteristic curve mode

UtilCrv2-DsaTrg

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Configuration of characteristic curve mode, 2nd characteristic curve > Deactivation threshold

0.000 to 100.000

10.000 

0.001

InstallerSMA Grid Guard

Parameter

Number of points to be used, conf. of grid integr. char. 2

UtilCrv2-NumPt

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Number of points to be used

1 to 8

1

InstallerSMA Grid Guard

Parameter

X value 1, conf. of grid integr. char. 2

UtilCrv2-XVal1

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 1

70.000 to 550.000

Depending on the country data set

0.001

InstallerSMA Grid Guard

Parameter

Y value 1, conf. of grid integr. char. 2

UtilCrv2-YVal1

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 1

−100.000 to +100.000

1.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 2, conf. of grid integr. char. 2

UtilCrv2-XVal2

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 2

70.000 to 550.000

Depending on the country data set

0.001

InstallerSMA Grid Guard

Parameter

Y value 2, conf. of grid integr. char. 2

UtilCrv2-YVal2

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 2

−100.000 to +100.000

0.850 

0.001

InstallerSMA Grid Guard

Parameter

X value 3, conf. of grid integr. char. 2

UtilCrv2-XVal3

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 3

70.000 to 550.000

484.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 3, conf. of grid integr. char. 2

UtilCrv2-YVal3

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 3

−100.000 to +100.000

0.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 4, conf. of grid integr. char. 2

UtilCrv2-XVal4

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 4

70.000 to 550.000

484.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 4, conf. of grid integr. char. 2

UtilCrv2-YVal4

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 4

−100.000 to +100.000

0.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 5, conf. of grid integr. char. 2

UtilCrv2-XVal5

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 5

70.000 to 550.000

484.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 5, conf. of grid integr. char. 2

UtilCrv2-YVal5

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 5

−100.000 to +100.000

0.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 6, conf. of grid integr. char. 2

UtilCrv2-XVal6

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 6

70.000 to 550.000

484.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 6, conf. of grid integr. char. 2

UtilCrv2-YVal6

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 6

−100.000 to +100.000

0.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 7, conf. of grid integr. char. 2

UtilCrv2-XVal7

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 7

70.000 to 550.000

484.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 7, conf. of grid integr. char. 2

UtilCrv2-YVal7

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 7

−100.000 to +100.000

0.000 

0.001

InstallerSMA Grid Guard

Parameter

X value 8, conf. of grid integr. char. 2

UtilCrv2-XVal8

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 8

70.000 to 550.000

484.000 

0.001

InstallerSMA Grid Guard

Parameter

Y value 8, conf. of grid integr. char. 2

UtilCrv2-YVal8

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 8

−100.000 to +100.000

0.000 

0.001

InstallerSMA Grid Guard

Parameter

Adjustment time of char. operating point, conf. of grid integration char. 2

UtilCrv2-CrvTms

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Adjustm. time characteristic curve operating point

0.0 s to 1000.0 s

0.0 s

0.1

InstallerSMA Grid Guard

Parameter

Decrease ramp, conf. of grid integration char. 2

UtilCrv2-RmpDec

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Decrease ramp

1.0 % to 10000.0 %

6.0 %

0.1

InstallerSMA Grid Guard

Parameter

Increase ramp, conf. of grid integration char. 2

UtilCrv2-RmpInc

Installer

System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Increase ramp

1.0 % to 10000.0 %

30.0 %

0.1

InstallerSMA Grid Guard

Parameter

Reference voltage, PV system control

VRef

Installer

AC Side > Inverter > PV system control > Reference voltage

80 V to 500 V

Depending on the country data set

1

InstallerSMA Grid Guard

Parameter

Reference correction voltage, PV system control

VRefOfs

Installer

AC Side > Inverter > PV system control > Reference correction voltage

−20 V to +20 V

0 V

1

InstallerSMA Grid Guard

Measured value

Grid frequency

GridMs.Hz

User

AC Side > Grid measurements > Grid frequency

Measured value

Operating condition grid frequency

User

AC Side > Grid measurements > Operating condition grid frequency

Measured value

Apparent power

GridMs.TotVA

User

AC Side > Grid measurements > Apparent power

Measured value

Normalized total apparent power

User

AC Side > Grid measurements > Normalized total apparent power

Measured value

Apparent power L1

GridMs.VA.phsA

User

AC Side > Grid measurements > Apparent power > Phase L1

Measured value

Apparent power L2

GridMs.VA.phsB

User

AC Side > Grid measurements > Apparent power > Phase L2

Measured value

Apparent power L3

GridMs.VA.phsC

User

AC Side > Grid measurements > Apparent power > Phase L3

Measured value

Reactive power

GridMs.TotVAr

User

AC Side > Grid measurements > Reactive power

Measured value

Operating condition reactive power

User

AC Side > Grid measurements > Operating condition reactive power

Measured value

Reactive power L1

GridMs.VAr.phsA

User

AC Side > Grid measurements > Reactive power > Phase L1

Measured value

Reactive power L2

GridMs.VAr.phsB

User

AC Side > Grid measurements > Reactive power > Phase L2

Measured value

Reactive power L3

GridMs.VAr.phsC

User

AC Side > Grid measurements > Reactive power > Phase L3

Measured value

Displacement power factor

GridMs.TotPF

User

AC Side > Grid measurements > Displacement power factor

Measured value

Power

Pac

User

AC Side > Grid measurements > Power

Measured value

Operating condition power

User

AC Side > Grid measurements > Operating condition power

Measured value

Power L1

GridMs.W.phsA

User

AC Side > Grid measurements > Power per phase > Phase L1

Measured value

Power L2

GridMs.W.phsB

User

AC Side > Grid measurements > Power per phase > Phase L2

Measured value

Power L3

GridMs.W.phsC

User

AC Side > Grid measurements > Power per phase > Phase L3

Measured value

Grid current phase L1

GridMs.A.phsA

User

AC Side > Grid measurements > Phase currents > Phase L1

Measured value

Operating condition current L1

User

AC Side > Grid measurements > Operating condition current > Phase L1

Measured value

Grid current phase L2

GridMs.A.phsB

User

AC Side > Grid measurements > Phase currents > Phase L2

Measured value

Operating condition current L2

User

AC Side > Grid measurements > Operating condition current > Phase L2

Measured value

Grid current phase L3

GridMs.A.phsC

User

AC Side > Grid measurements > Phase currents > Phase L3

Measured value

Operating condition current L3

User

AC Side > Grid measurements > Operating condition current > Phase L3

Measured value

Operating state grid voltage L1 against L2

GridMs.VNom.A2B

User

AC Side > Grid measurements > Operating condition voltage > Phase L1 against L2

Measured value

Grid voltage phase L1 against L2

GridMs.PhV.A2B

User

AC Side > Grid measurements > Phase voltage > Phase L1 against L2

Measured value

Operating state grid voltage L2 against L3

GridMs.VNom.B2C

User

AC Side > Grid measurements > Operating condition voltage > Phase L2 against L3

Measured value

Grid voltage phase L2 against L3

GridMs.PhV.B2C

User

AC Side > Grid measurements > Phase voltage > Phase L2 against L3

Measured value

Operating state grid voltage L3 against L1

GridMs.VNom.C2A

User

AC Side > Grid measurements > Operating condition voltage > Phase L3 against L1

Measured value

Grid voltage phase L3 against L1

GridMs.PhV.C2A

User

AC Side > Grid measurements > Phase voltage > Phase L3 against L1

Parameter

Maximum active power device

Plimit

User

Device > Inverter > Maximum active power

Depending on the device type

25,000 W

1

Parameter

Set active power limit

Pmax

Installer

Device > Inverter > Currently set active power limit

Depending on the device type

25,000 W

1

Installer

Parameter

Active power gradient

WGra

Installer

System and device control > Inverter > Active power gradient

1 % to 1000 %

20 %

1

InstallerSMA Grid Guard

Parameter

Deactivation delay

Inv.StopTms

Installer

Device > Inverter > Deactivation delay

1 s to 3600 s

2 s

1

Installer

Parameter

End point of the power control via frequency

OffGri.HzdLim

Installer

AC Side > Inverter > Island mode > End point of the power control via frequency

0.00 Hz to 5.00 Hz

2.00 Hz

0.01

Installer

Parameter

Start. point of the power control via frequency

OffGri.HzdStr

Installer

AC Side > Inverter > Island mode > Start point of the power control via frequency

0.00 Hz to 5.00 Hz

1.00 Hz

0.01

Installer

Parameter

Currently set apparent power limit

Smax

Installer

Device > Inverter > Currently set apparent power limit

Depending on the device type

25,000 VA

1

Installer

Parameter

Maximum apparent power device

Slimit

Installer

Device > Inverter > Maximum apparent power

Depending on the device type

25,000 VA

1

Parameter

Reactive power gradient

VArGra

Installer

System and device control > Inverter > Reactive power gradient

1 % to 50 %

20 %

1

InstallerSMA Grid Guard

Measured value

Residual current

Iso.FltA

Installer

DC Side > Insulation monitoring > Residual current

Measured value

Operating condition residual current

User

DC Side > Insulation monitoring > Operating condition residual current

Measured value

Insulation resistance

Riso

Installer

DC Side > Insulation monitoring > Insulation resistance

Measured value

Operating condition insulation resistance

User

DC Side > Insulation monitoring > Operating condition insulation resistance

Measured value

Operating time

Mt.TotTmh

User

AC Side > Measured values > Operating time

Parameter

Set total operating time at grid connection point

Mt.TotTmhSet

Installer

AC Side > Measured values > Set operating time

0 h to 440000 h

0 h

1

Installer

Measured value

Feed-in time

Mt.TotOpTmh

User

AC Side > Measured values > Feed-in time

Parameter

Set total feed-in time at the grid connection pt.

Mt.TotOpTmhSet

Installer

AC Side > Measured values > Set feed-in time

0 h to 440000 h

0 h

1

Installer

Measured value

Total yield

E-Total

User

AC Side > Measured values > Total yield

Parameter

Set total yield

Mt.TotkWhSet

User

AC Side > Measured values > Set total yield

0 kWh to 4000000 kWh

0 kWh

1

User

Parameter

Communication version

ComRev

Installer

Type Label > Type Label > Communication version

0 to 4294967294

1

Parameter

Serial number

SerNumSet, Serial Number

User

Type Label > Type Label > Serial number

0 to 4294967294

1

Parameter

Firmware version of the main processor

HP.swRev

User

Device Components > Type Label > Main processor > Software version

0 to 4294967294

1

Parameter

Hardware version of the main processor

HP.hwRev

Installer

Device Components > Type Label > Main processor > Hardware version

0 to 4294967294

1

Parameter

Revision status of the main processor

HP.RevVer

Installer

Device Components > Type Label > Main processor > Revision status

0 to 255

1

Parameter

Serial number of the main processor

CmpMain.SerNum

Installer

Device Components > Type Label > Main processor > Serial number

0 to 4294967294

1

Parameter

SUSyID of the main processor

CmpMain.SusyId

Installer

Device Components > Type Label > Main processor > SUSyID

0 to 4294967294

1

Parameter

Firmware version of the logic component

CPLD.swRev

Installer

Device Components > Type Label > Logic component > Software version

0 to 4294967294

1

Parameter

Revision status of the logic component

CPLD.RevVer

Installer

Device Components > Type Label > Logic component > Revision status

0 to 255

1

Measured value

Number of grid connections

Op.GriSwCnt

Installer

AC Side > Operation > N° grid conn. at grid conn.pt.

Parameter

Active power limitation P, active power configuration

P-W

Installer

System and device control > Inverter > Configuration of feed-in management > Configuration of active power P limitation > Power per phase

Depending on the device type

25,000 W

1

InstallerSMA Grid Guard

Parameter

Active power limitation P, active power configuration

P-WNom

Installer

System and device control > Inverter > Configuration of feed-in management > Configuration of active power P limitation > Power per phase

0 % to 100 %

100 %

1

InstallerSMA Grid Guard

Parameter

Reactive power set value as a %

Q-VArNom

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Config. of reactive power Q, direct specification > Reactive power setpoint Q

−100.0 % to +100.0 %

0.0 %

0.1

InstallerSMA Grid Guard

Parameter

Specified voltage UQ0, reactive power/voltage characteristic curve configuration Q(U)

Q-VolRefNom

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Specified voltage UQ0

80 % to 120 %

100 %

1

InstallerSMA Grid Guard

Parameter

Symmetrical limit for maximum reactive power, reactive power/voltage characteristic curve configuration Q(U)

Q-VArMaxNom

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Symmetrical limit for maximum reactive power

0.0 % to 50.0 %

0.0 %

0.1

InstallerSMA Grid Guard

Parameter

Voltage spread, reactive power/voltage characteristic curve configuration Q(U)

Q-VolWidNom

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Voltage spread

0.0 % to 20.0 %

0.0 %

0.1

InstallerSMA Grid Guard

Parameter

Reactive power gradient, reactive power/voltage characteristic curve configuration Q(U)

Q-VArGraNom

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Reactive power gradient

0.0 % to 10.0 %

0.0 %

0.1

InstallerSMA Grid Guard

Parameter

Adjustment time for characteristic operating point, reactive power/voltage characteristic curve configuration Q(U)

Q-VArTms

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Adjustment time for charact. curve operating point

2 s to 60 s

10 s

1

InstallerSMA Grid Guard

Parameter

PWM inversion delay, dynamic grid support configuration

DGS-PWMTms

Installer

System and device control > Inverter > Configuration of dynamic grid support > PWM inversion delay

0.00 s to 5.00 s

0.00 s

0.01

InstallerSMA Grid Guard

Parameter

Gradient K of the reactive current droop, full dynamic grid support configuration

DGS-ArGraNomPrc

Installer

System and device control > Inverter > Configuration of dynamic grid support > Configuration of full dynamic grid support > Gradient K of the reactive current droop

0.00 % to 10.00 %

2.00 %

0.01

InstallerSMA Grid Guard

Parameter

Lower limit, voltage dead band, full dynamic grid support configuration

DGS-DbVolNomMin

Installer

System and device control > Inverter > Configuration of dynamic grid support > Configuration of full dynamic grid support > Lower limit, voltage dead band

−40 % to 0 %

−10 %

1

InstallerSMA Grid Guard

Parameter

Upper limit, voltage dead band, full dynamic support configuration

DGS-DbVolNomMax

Installer

System and device control > Inverter > Configuration of dynamic grid support > Configuration of full dynamic grid support > Upper limit, voltage dead band

0 % to 40 %

10 %

1

InstallerSMA Grid Guard

Parameter

Normalized reactive power limitation by PV system ctrl

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power mode of PV system control > Reactive power setpoint Q

Installer

Parameter

Active power limitation by PV system control

Installer

System and device control > Inverter > Configuration of feed-in management > Configuration of active power mode of PV system ctrl > Power per phase

Installer

Parameter

Normalized active power limitation by PV system ctrl

Installer

System and device control > Inverter > Configuration of feed-in management > Configuration of active power mode of PV system ctrl > Power per phase

Installer

Parameter

Dis.pow.factor that can be changed via PV system ctrl

Installer

System and device control > Inverter > Configuration of static voltage stabilization > cosPhi config. method of PV system control > cosPhi specification

Installer

Parameter

Cycle time of the OptiTrac Global Peak algorithm

MPPShdw.CycTms

Installer

DC Side > DC settings > OptiTrac Global Peak > Cycle time

360 s to 1800 s

360 s

1

Installer

Parameter

Timeout for absent active power limitation

WCtlCom.TmsOut

Installer

System and device control > Inverter > Configuration of system control via communication > Act. power lim. via PV system ctrl > Timeout

5 s to 86400 s

600 s

1

Installer

Parameter

Fallback act power lmt P in % of WMax for absent act power lmt

WCtlCom.FlbNom

Installer

System and device control > Inverter > Configuration of system control via communication > Act. power lim. via PV system ctrl > Fallback active power P

0.00 % to 100.00 %

100.00 %

0.01

Installer

Parameter

Timeout for absent reactive power control

QCtlCom.TmsOut

Installer

System and device control > Inverter > Configuration of system control via communication > Q specified by PV system control > Timeout

5 s to 86400 s

600 s

1

Installer

Parameter

Fallback react power Q in % of WMax for absent react power ctr

QCtlCom.FlbNom

Installer

System and device control > Inverter > Configuration of system control via communication > Q specified by PV system control > Fallback reactive power Q

−50.00 % to +50.00 %

0.00 %

0.01

Installer

Parameter

Timeout for absent cos Phi spec

PFCtlCom.TmsOut

Installer

System and device control > Inverter > Configuration of system control via communication > cosPhi, specified by PV system control > Timeout

5 s to 86400 s

600 s

1

Installer

Parameter

Fallback cos Phi for absent cos Phi spec

PFCtlCom.Flb

Installer

System and device control > Inverter > Configuration of system control via communication > cosPhi, specified by PV system control > Fallback cos Phi

0.8000 to 1.0000

1.0000 

0.0001

Installer

Measured value

Current spec. active power limitation P

Op.Dmd.WCtl

User

System and device control > Operation > Specification > Active power limitation P

Measured value

Current spec. reactive power Q

Op.Dmd.VArCtl

User

System and device control > Operation > Specification > Reactive power Q

Measured value

Current spec. cos Phi

Op.Dmd.PFCtl

User

System and device control > Operation > Specification > cos Phi

Parameter

Char. curve no. for dyn. network disconnect

DynDsconCrvNum

Installer

System and device control > Inverter > Dynamic network disconnection > Characteristic curve number

0 to 2

1

InstallerSMA Grid Guard

Parameter

Tripping time for active power limitation

P-WCtlTmms

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Tripping time for active power limitation

0 ms to 60000 ms

0 ms

1

InstallerSMA Grid Guard

Parameter

Ripple control signal detection, amplification of narrow-band support

RplDet-NBS-Gain

Installer

Device > Inverter > Ripple control signal detection > Narrow-band support > Amplification

−1000.00 V/A to +1000.00 V/A

0.00 V/A

0.01

Installer

Parameter

Ripple control signal detection, damping of narrow-band support

RplDet-NBS-Damp

Installer

Device > Inverter > Ripple control signal detection > Narrow-band support > Damping

−10.00 to +10.00

0.10 

0.01

Installer

Parameter

Ripple control signal detection, frequency of narrow-band support

RplDet-NBS-Hz

Installer

Device > Inverter > Ripple control signal detection > Narrow-band support > Grid frequency

100.0 Hz to 2000.0 Hz

1,000.0 Hz

0.1

Installer

Parameter

Rated apparent power of all inverters

Plnt.VARtg

User

Grid connection > PV system > Nominal apparent voltage

1 VA to 4000000000 VA

25,000 VA

1

Installer

Parameter

Ohmic resistance for impedance compensation

ImpCpn.OhmRis

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Impedance compensation > Ohmic resistance

0.0000 to 10.0000

0.0000 

0.0001

Installer

Parameter

Inductive resistance for impedance compensation

ImpCpn.IndRis

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Impedance compensation > Inductive resistance

0.0000 to 10.0000

0.0000 

0.0001

Installer

Parameter

Capacitive resistance for impedance compensation

ImpCpn.CapacRis

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Impedance compensation > Capacitive resistance

0.00 to 40000000.00

40,000,000.00 

0.01

Installer

Measured value

Speedwire connection status of SMACOM A

User

System communication > Speedwire > SMACOM A > Status

  • Fault (Alm)
  • Ok (Ok)
  • Warning (Wrn)
  • No connection (NotConn)

No connection (NotConn)

-

Measured value

Connection speed of SMACOM A

User

System communication > Speedwire > SMACOM A > Connection speed

  • ------- (None)
  • 10 Mbit/s (ConnSpd10)
  • 100 Mbit/s (ConnSpd100)

------- (None)

-

Measured value

Duplex mode of SMACOM A

Installer

System communication > Speedwire > SMACOM A > Duplex mode

  • ------- (None)
  • Half duplex (HalfDpx)
  • Full duplex (FulDpx)

------- (None)

-

Measured value

Speedwire connection status of SMACOM B

User

System communication > Speedwire > SMACOM B > Status

  • Fault (Alm)
  • Ok (Ok)
  • Warning (Wrn)
  • No connection (NotConn)

No connection (NotConn)

-

Measured value

Connection speed of SMACOM B

User

System communication > Speedwire > SMACOM B > Connection speed

  • ------- (None)
  • 10 Mbit/s (ConnSpd10)
  • 100 Mbit/s (ConnSpd100)

------- (None)

-

Measured value

Duplex mode of SMACOM B

Installer

System communication > Speedwire > SMACOM B > Duplex mode

  • ------- (None)
  • Half duplex (HalfDpx)
  • Full duplex (FulDpx)

------- (None)

-

Parameter

Automatic speedwire configureation switched on

User

System communication > Speedwire > Automatic configuration switched on

  • Yes (Yes)
  • No (No)

Yes (Yes)

User

-

Parameter

Modbus TCP server on

User

External Communication > Modbus > TCP server > Activated

  • Yes (Yes)
  • No (No)

No (No)

Installer

-

Parameter

Modbus UDP server on

User

External Communication > Modbus > UDP server > Activated

  • Yes (Yes)
  • No (No)

No (No)

Installer

-

Parameter

Goose application ID

GOOSE-GoAppId

Installer

External Communication > IEC 61850 configuration > GOOSE configuration > Application-ID

0 to 16384

16,384 

1

InstallerSMA Grid Guard

Parameter

Modbus TCP server port

User

External Communication > Modbus > TCP server > Port

1 to 65535

502 

1

Installer

Parameter

Modbus UDP server port

User

External Communication > Modbus > UDP server > Port

1 to 65535

502 

1

Installer